{ "@context": "https://schema.org", "@graph": [ { "@type": "LocalBusiness", "@id": "https://industrialfiretx.com/#business", "name": "Industrial Fire", "alternateName": ["Industrial Fire TX", "Industrial Fire Equipment Co."], "url": "https://industrialfiretx.com/", "logo": { "@id": "https://industrialfiretx.com/#logo" }, "image": { "@id": "https://industrialfiretx.com/#logo" }, "telephone": "+1-713-223-9181", "slogan": "Serving Texas since 1945", "description": "Family-owned commercial and industrial fire protection contractor in Houston, TX since 1945. Industrial Fire provides fire suppression, fire alarms, extinguisher service, and fire-code compliance for restaurants, data centers, schools, healthcare, manufacturing, food trucks, and commercial facilities.", "address": { "@type": "PostalAddress", "streetAddress": "204 N Palmer St", "addressLocality": "Houston", "addressRegion": "TX", "postalCode": "77003", "addressCountry": "US" }, "areaServed": [ { "@type": "City", "name": "Houston" }, { "@type": "AdministrativeArea", "name": "Harris County, TX" }, { "@type": "AdministrativeArea", "name": "Greater Houston, TX" } ], "knowsAbout": [ "ANSUL fire suppression systems", "Amerex fire suppression", "Pyro-Chem systems", "Kidde fire systems", "Buckeye fire equipment", "Commercial kitchen fire suppression", "Restaurant hood suppression", "Fire extinguisher inspection and recharge", "Fire alarm monitoring and inspection", "Clean agent and CO2 suppression", "NFPA 10", "NFPA 96", "Fire code compliance" ], "identifier": [ { "@type": "PropertyValue", "name": "License", "value": "ECR-2061363" }, { "@type": "PropertyValue", "name": "License", "value": "ACR-2368800" }, { "@type": "PropertyValue", "name": "License", "value": "B10568601" }, { "@type": "PropertyValue", "name": "License", "value": "HCR-2215410" }, { "@type": "PropertyValue", "name": "License", "value": "RIN-A436" } ], "hasOfferCatalog": { "@type": "OfferCatalog", "name": "Fire Protection Services", "itemListElement": [ { "@type": "OfferCatalog", "name": "Fire Suppression Systems" }, { "@type": "OfferCatalog", "name": "Fire Alarm Systems" }, { "@type": "OfferCatalog", "name": "Fire Extinguisher Services" }, { "@type": "OfferCatalog", "name": "Fire Protection Systems" }, { "@type": "OfferCatalog", "name": "Fire Compliance & Inspections" } ] }, "sameAs": ["https://www.linkedin.com/company/industrialfire/"], "priceRange": "$$", "openingHoursSpecification": [ { "@type": "OpeningHoursSpecification", "dayOfWeek": ["Monday","Tuesday","Wednesday","Thursday","Friday"], "opens": "08:00", "closes": "15:30" }, { "@type": "OpeningHoursSpecification", "dayOfWeek": ["Monday","Tuesday","Wednesday","Thursday","Friday","Saturday","Sunday"], "opens": "00:00", "closes": "23:59", "description": "24/7 emergency service" } ], "geo": { "@type": "GeoCoordinates", "latitude": 29.7549158, "longitude": -95.3395642 } }, { "@type": "ImageObject", "@id": "https://industrialfiretx.com/#logo", "url": "https://eujrrhno5sm.exactdn.com/wp-content/uploads/2026/05/industrial-fire-logo-white.png", "contentUrl": "https://eujrrhno5sm.exactdn.com/wp-content/uploads/2026/05/industrial-fire-logo-white.png", "caption": "Industrial Fire" }, { "@type": "WebSite", "@id": "https://industrialfiretx.com/#website", "url": "https://industrialfiretx.com/", "name": "Industrial Fire", "publisher": { "@id": "https://industrialfiretx.com/#business" }, "inLanguage": "en-US", "potentialAction": { "@type": "SearchAction", "target": { "@type": "EntryPoint", "urlTemplate": "https://industrialfiretx.com/?s={search_term_string}" }, "query-input": "required name=search_term_string" } }, { "@type": "BlogPosting", "@id": "https://industrialfiretx.com/do-fire-extinguishers-expire/#article", "headline": "Do Fire Extinguishers Expire?", "url": "https://industrialfiretx.com/do-fire-extinguishers-expire/", "datePublished": "2026-09-15T09:37:34", "dateModified": "2026-09-17T13:11:29", "author": { "@id": "https://industrialfiretx.com/#business" }, "publisher": { "@id": "https://industrialfiretx.com/#business" }, "mainEntityOfPage": { "@id": "https://industrialfiretx.com/do-fire-extinguishers-expire/#webpage" }, "inLanguage": "en-US", "image": { "@type": "ImageObject", "url": "https://eujrrhno5sm.exactdn.com/wp-content/uploads/2026/07/worker-holding-fire-extinguisher-industrial-fire-safety-.webp", "width": 1463, "height": 1004 } }, { "@type": "WebPage", "@id": "https://industrialfiretx.com/do-fire-extinguishers-expire/#webpage", "url": "https://industrialfiretx.com/do-fire-extinguishers-expire/", "name": "Do Fire Extinguishers Expire?", "isPartOf": { "@id": "https://industrialfiretx.com/#website" }, "breadcrumb": { "@id": "https://industrialfiretx.com/do-fire-extinguishers-expire/#breadcrumb" }, "hasPart": { "@id": "https://industrialfiretx.com/do-fire-extinguishers-expire/#faq" }, "inLanguage": "en-US" }, { "@type": "BreadcrumbList", "@id": "https://industrialfiretx.com/do-fire-extinguishers-expire/#breadcrumb", "itemListElement": [ { "@type": "ListItem", "position": 1, "name": "Home", "item": "https://industrialfiretx.com/" }, { "@type": "ListItem", "position": 2, "name": "Blog", "item": "https://industrialfiretx.com/blog/" }, { "@type": "ListItem", "position": 3, "name": "Do Fire Extinguishers Expire?", "item": "https://industrialfiretx.com/do-fire-extinguishers-expire/" } ] }, { "@type": "FAQPage", "@id": "https://industrialfiretx.com/do-fire-extinguishers-expire/#faq", "url": "https://industrialfiretx.com/do-fire-extinguishers-expire/", "inLanguage": "en-US", "isPartOf": { "@id": "https://industrialfiretx.com/do-fire-extinguishers-expire/#webpage" }, "mainEntity": [ { "@type": "Question", "name": "Do fire extinguishers have an expiration date?", "acceptedAnswer": { "@type": "Answer", "text": "Most portable fire extinguishers carry no printed expiration date on the cylinder. What they do have is a manufacture date stamped on the collar and a mandatory maintenance schedule under NFPA 10. When those maintenance intervals lapse, specifically the six-year internal examination or the required hydrostatic test, the extinguisher is effectively out of compliance whether or not a date reads expired. A green gauge alone does not confirm that an older extinguisher remains safe or serviceable." } }, { "@type": "Question", "name": "How long does a fire extinguisher last?", "acceptedAnswer": { "@type": "Answer", "text": "Service life varies by type. Dry chemical extinguishers typically last 12 years before requiring hydrostatic testing; CO2 cylinders must be tested at 5-year intervals but can remain in service for 20 or more years with proper maintenance. Water, foam, and wet chemical kitchen extinguishers generally follow a 5-year hydrostatic testing schedule. All types require annual professional maintenance under NFPA 10. A well-maintained commercial unit can outlast a neglected one by decades." } }, { "@type": "Question", "name": "Where is the date on a fire extinguisher?", "acceptedAnswer": { "@type": "Answer", "text": "Look in three places: the neck or collar of the cylinder, where the manufacture date is often stamped or embossed into the metal; the label, where some manufacturers print the date; and the service tag, which shows a punched hole for the month and year of each professional inspection. No legible manufacture date means no documented history. Take the unit to a licensed technician for evaluation before returning it to service." } }, { "@type": "Question", "name": "Is a 20-year-old fire extinguisher still good?", "acceptedAnswer": { "@type": "Answer", "text": "It depends entirely on its maintenance history. NFPA 10 sets no absolute age limit, but a 20-year-old unit must have passed both its six-year internal examination and at least one hydrostatic test on schedule to be considered serviceable. A commercial-grade Amerex or ANSUL extinguisher that has been professionally maintained with records to show it can pass inspection at 20 years and remain in service. One that has never been serviced should be retired and replaced." } }, { "@type": "Question", "name": "Can an expired fire extinguisher be recharged?", "acceptedAnswer": { "@type": "Answer", "text": "In some cases, yes. If the cylinder passes hydrostatic testing, an NFPA 10-compliant technician can recharge and return it to service. The unit must first undergo internal examination if the six-year interval has passed. If the cylinder shows corrosion, structural defects, or fails pressure testing, recharging is not permitted and replacement is required." } }, { "@type": "Question", "name": "Who is allowed to service a fire extinguisher in Texas?", "acceptedAnswer": { "@type": "Answer", "text": "Under Texas Administrative Code Title 28 Chapter 34 Section 34.5, only technicians licensed by the Texas State Fire Marshal's Office may perform annual maintenance, six-year internal examinations, and hydrostatic testing on portable fire extinguishers. Industrial Fire holds the required Texas licenses (ECR-2061363 and ACR-2368800) and has been performing licensed extinguisher service in Houston since 1945." } } ] } ] }

Do Fire Extinguishers Expire? 

This page explains whether fire extinguishers expire and how long they actually last. Most portable extinguishers carry no printed expiration date on the cylinder, but every unit has a finite service life and mandatory maintenance intervals set by governing standards. The two primary standards are NFPA 10 (Standard for Portable Fire Extinguishers) and OSHA 29 CFR 1910.157, which establishes workplace requirements for inspection, maintenance, and testing. The sections below cover service life by extinguisher type, hydrostatic testing intervals, the six-year internal maintenance requirement, how to read the manufacture date stamp and service tag, and when to recharge versus replace a unit. This content was written by Industrial Fire, a licensed Houston fire protection contractor serving the Houston area since 1945, holding Texas licenses ECR-2061363 and ACR-2368800.

Do fire extinguishers actually expire?

Most portable fire extinguishers carry no printed expiration date, but every unit has a finite service life and mandatory maintenance intervals established by NFPA 10. When those intervals lapse without documented service, the extinguisher is effectively out of compliance regardless of how it looks. A green pressure gauge indicates current pressure, not whether the cylinder interior, extinguishing agent, or valve components are sound.

Dry chemical powder can cake inside the cylinder over time. Seals age and allow slow pressure loss. Valve components corrode. An untouched extinguisher with a green gauge can still be an unreliable tool in an actual fire. Industrial Fire has served Houston since 1945 and routinely evaluates units that appear unused but are years overdue for required maintenance.

Non-rechargeable, disposable extinguishers have a manufacturer-stated service limit after which they must be replaced and cannot be refilled. Rechargeable extinguishers may remain in service only when they pass required maintenance, internal examinations where applicable, and hydrostatic testing on schedule under NFPA 10 and the manufacturer’s instructions.

How long does a fire extinguisher last, by type

Fire extinguisher in a wall cabinet representing service life and replacement by extinguisher type.

Service life depends on extinguisher type, cylinder material, and maintenance history. NFPA 10 sets the mandatory inspection, maintenance, and hydrostatic testing intervals for each class of portable extinguisher. The table below summarizes typical service life and testing requirements by type.

Extinguisher Type Typical Service Life Hydrostatic Test Interval 6-Year Internal Maintenance Rechargeable
Dry chemical (stored pressure) 12 years 12 years Yes Yes
Dry chemical (cartridge/cylinder) 12 years 12 years Yes Yes
CO2 20+ years 5 years Yes Yes
Water/Water mist 5-6 years 5 years Yes Yes
Foam (AFFF/FFFP) 5-6 years 5 years Yes Yes
Wet chemical (Class K) 5-6 years 12 years Yes Yes
Clean agent (Halotron, etc.) 10-20 years 5 years Yes Yes

Dry chemical stored-pressure units are the most common type in commercial settings. They typically last 12 years before hydrostatic testing is required, and they require a six-year internal examination under NFPA 10 Section 7.4. CO2 cylinders can remain in service for 20 or more years with proper maintenance, though they face hydrostatic testing every 5 years. Water, foam, and wet chemical kitchen units typically have shorter service life and follow a 5-year hydrostatic testing schedule.

All extinguisher types require monthly visual inspections and annual professional maintenance under NFPA 10. The manufacture date stamped on the cylinder, not the date your business purchased the unit, starts the maintenance clock.

What NFPA 10 actually requires

NFPA 10 (Standard for Portable Fire Extinguishers) is the primary national standard governing portable extinguisher inspection, maintenance, testing, and retirement. The standard establishes four mandatory service intervals that every commercial facility must follow:

Monthly visual inspection (NFPA 10 Section 7.2): A designated person must visually check each extinguisher every 30 days to confirm it is in its designated location, has not been tampered with, shows no obvious physical damage, and has a gauge in the operable range.

Annual professional maintenance (NFPA 10 Section 7.3): A licensed technician must perform a complete maintenance check at least once per year, covering all mechanical parts, extinguishing agent, and expellant, with a thorough examination of each component.

Six-year internal examination (NFPA 10 Section 7.4): Stored-pressure dry chemical extinguishers require internal examination at six-year intervals. A licensed technician disassembles the unit, inspects the cylinder interior and internal components, replaces or repairs damaged parts, and reseals the extinguisher with a tamper-evident indicator.

Hydrostatic testing (NFPA 10 Section 8): All cylinders must be hydrostatically tested at intervals based on type. CO2, water, foam, and clean agent cylinders are tested every 5 years. Dry chemical and wet chemical cylinders are tested every 12 years. Any cylinder that fails hydrostatic testing must be removed from service and destroyed.

OSHA 29 CFR 1910.157(e)(3) requires employers to perform annual maintenance checks and maintain records of those inspections. Both NFPA 10 and OSHA requirements apply in most commercial facilities and work together rather than separately.

In Texas, only licensed technicians may perform the six-year internal maintenance and hydrostatic testing on portable fire extinguishers. Texas Administrative Code Title 28 Chapter 34 Section 34.5 specifies that fire extinguisher service work must be performed by personnel licensed by the Texas State Fire Marshal’s Office. Industrial Fire holds the required Texas licenses and has been providing licensed fire extinguisher service in Houston since 1945.

How to read the date on your fire extinguisher

Technician checking fire extinguisher records to verify the manufacture and inspection date.

Knowing your extinguisher’s age is the first step in determining whether it is in compliance. The manufacture date is typically found in three places: stamped or embossed on the cylinder neck or collar near the valve assembly; printed on the nameplate label, where some manufacturers include a date code; or indicated on the service tag attached to the handle.

The service tag uses a punch-mark system. A hole is punched through the corresponding month and year of each professional inspection, creating a physical record of maintenance visits. The tag shows the inspection history, but it is not the manufacture date. The manufacture date comes from the cylinder itself, stamped into the metal.

When no legible manufacture date can be found, treat the unit as having an unknown age and unknown service history. Do not leave it in service. Bring it to a licensed Houston fire extinguisher service company for professional evaluation.

Industrial Fire operates a walk-in counter at 204 N Palmer St, Houston TX 77003, open Monday through Friday, 8:00 a.m. to 3:30 p.m. Customers can bring extinguishers of unknown age directly to the counter for evaluation by a licensed technician.

The fire extinguisher lifecycle: what to expect by age

Years 1 to 5: Annual inspections and monthly visual checks

During the first five years of a fire extinguisher’s life, the primary maintenance requirements under NFPA 10 are monthly visual inspections (Section 7.2) and annual professional maintenance (Section 7.3). The extinguisher should hold pressure with the gauge in the green zone, show no visible corrosion, dents, or physical damage, and have an intact hose, pull pin, and tamper seal. Service records should be current and on file. At this stage, a well-maintained unit requires no major service beyond the annual check. Keep the extinguisher accessible, properly mounted, and documented.

Years 6 to 12: Six-year internal examination

At the six-year mark, NFPA 10 Section 7.4 triggers the six-year internal examination for stored-pressure dry chemical units. This is more than a visual check. A licensed technician disassembles the extinguisher, inspects the interior of the cylinder, checks the condition of the valve and internal parts, replaces worn components, verifies the agent is dry and free of caking, and reassembles and reseals the unit with a tamper-evident indicator.

Even extinguishers that have never been used can accumulate internal issues during this period. Agent can settle and cake over time, valves can corrode, and internal parts degrade with age. Skipping the six-year internal exam leaves a unit that may appear serviceable but cannot be verified as reliable.

Years 12 to 20: Hydrostatic testing

At 12 years, NFPA 10 Section 8 requires hydrostatic testing for dry chemical and wet chemical cylinders. CO2, water, foam, and clean agent extinguishers reach their first hydrostatic test at 5 years and continue on a 5-year cycle thereafter. Hydrostatic testing subjects the cylinder to pressure above its rated working pressure to verify structural integrity. A cylinder that fails must be condemned and destroyed.

At this stage, the condition of individual units varies widely. A well-maintained commercial unit from a manufacturer such as ANSUL or Amerex may still have many years of serviceable life ahead. A neglected unit may require replacement even if it passes hydrostatic testing, because internal corrosion or component deterioration may render it unreliable.

Beyond 20 years: Condition and records determine serviceability

NFPA 10 sets no absolute age limit for portable fire extinguishers. The standard does not automatically condemn a unit at 20 or 30 years of age. What the standard requires is that the unit pass every scheduled hydrostatic test and internal examination on time, with documented records. A hydrostatic test failure at any point requires retirement and destruction of the cylinder.

At Industrial Fire’s walk-in counter, technicians see 20- and 30-year-old commercial-grade extinguishers that pass hydrostatic testing and return to service, and disposable residential units from the same era that cannot be serviced at all. Age is a factor, but documented maintenance history and test results are the deciding factors.

How old is too old?

NFPA 10 sets no absolute age limit for portable fire extinguishers. There is no point at which the standard automatically requires retirement based solely on years of age. However, the cumulative effect of missed maintenance intervals, internal corrosion, caked agent, and undetected structural degradation makes very old extinguishers statistically unreliable, particularly those with gaps in their service records.

The practical answer for most commercial operators: if you cannot document that a unit passed its six-year internal examination and hydrostatic test on schedule, treat it as out of compliance regardless of how old it is. A 20-year-old extinguisher from Amerex or ANSUL that has been professionally maintained on schedule, with records to prove it, may pass current hydrostatic testing and remain in active service. A 10-year-old extinguisher that has never been serviced is already overdue for its six-year internal exam and may be operating without verified structural integrity.

Licensed technicians in Houston can determine serviceability in a single inspection. The decision is based on condition, documentation, and test results, not age alone.

Can an expired fire extinguisher still work?

Maybe, but the point of a fire extinguisher is that it must work reliably when seconds matter. A pressure gauge only shows whether the cylinder holds pressure at that moment. It cannot tell you whether the dry chemical agent has caked solid, whether the CO2 has been slowly leaking through a deteriorated seal, or whether the valve will open correctly under fire conditions.

An extinguisher that appears fully charged may deliver nothing when the pin is pulled, discharge at reduced pressure, or fail to operate because a corroded valve sticks. In an active fire, partial performance or total failure is not an acceptable outcome.

Remove any extinguisher from service that is past a required maintenance interval, shows corrosion or physical damage, has a gauge outside the green zone, or lacks documented service records. Have a licensed technician evaluate it before returning it to use.

What happens if you use an expired fire extinguisher?

In an emergency, an expired extinguisher may fail to discharge, discharge at reduced pressure, or deliver an agent that has degraded below effective concentration. The structural failure risk in a fire is low but not zero, particularly for cylinders that have missed hydrostatic testing over a long period.

For commercial facilities, the consequences extend beyond the fire itself. Under OSHA 29 CFR 1910.157, employers must maintain portable fire extinguishers in fully charged and operable condition and ensure they are inspected and maintained on schedule. Relying on an expired, untested, or unserviced unit in an emergency does not relieve liability. A post-incident investigation that identifies deferred maintenance as a contributing factor can increase legal and financial exposure significantly.

Under Texas Administrative Code, operating with out-of-compliance extinguishers is a citable violation during State Fire Marshal inspections. Texas fire code enforcement includes extinguisher compliance as part of routine commercial inspections. The safest position for any commercial operator: every extinguisher in service has a current inspection tag, documented service records, and is confirmed to have passed all required testing on schedule.

Recharge, test or replace: how to decide

Not every aging extinguisher needs to be replaced. Not every used extinguisher can simply be recharged and returned to service. The right path depends on the unit’s age, condition, type, and service history. Use this decision path:

  • Used it? Recharge immediately, regardless of age. NFPA 10 requires rechargeable extinguishers to be professionally recharged after any use, including a brief discharge.
  • Under 12 years old, pressure good, no visible damage, service records current? Schedule the six-year internal exam if due; otherwise proceed with annual maintenance only.
  • 12 or more years old with no documented hydrostatic test on record? Hydrostatic testing is required before the unit can remain in service.
  • Visible corrosion, cracked hose, missing tag, illegible label, or damaged valve? Replace the unit. No amount of recharging repairs structural defects.
  • Small 2.5 lb ABC unit? Replacement is often more economical than the combined cost of professional recharging and internal examination.

For cost considerations, two dedicated resources cover this in detail: Is it cheaper to recharge or replace a fire extinguisher? covers the recharge-versus-replace decision, and what a recharge typically costs breaks down the service pricing.

Your extinguisher has expired. Now what?

If your extinguisher is out of compliance, overdue for service, or has reached the end of serviceable life, you have two primary paths: professional recharging and return to service, or fire extinguisher replacement with a new compliant unit. A licensed technician evaluates the cylinder and determines which option applies based on condition, test results, and the unit’s maintenance history.

If the cylinder can be recharged after passing required internal examination and hydrostatic testing, schedule that service through a licensed Houston provider.

If the cylinder is corroded, has failed or cannot pass hydrostatic testing, is a non-rechargeable disposable unit, or is otherwise unserviceable, replacement is the appropriate path.

If the unit cannot be recharged and is truly at end of life, never put it in the trash. Pressurized cylinders require proper handling. Industrial Fire can advise on how to dispose of a fire extinguisher safely and in compliance with applicable requirements.

Frequently asked questions

Do fire extinguishers have an expiration date?

Most portable fire extinguishers carry no printed expiration date on the cylinder. What they do have is a manufacture date stamped on the collar and a mandatory maintenance schedule under NFPA 10. When those maintenance intervals lapse, specifically the six-year internal examination or the required hydrostatic test, the extinguisher is effectively out of compliance whether or not a date reads expired. A green gauge alone does not confirm that an older extinguisher remains safe or serviceable.

How long does a fire extinguisher last?

Service life varies by type. Dry chemical extinguishers typically last 12 years before requiring hydrostatic testing; CO2 cylinders must be tested at 5-year intervals but can remain in service for 20 or more years with proper maintenance. Water, foam, and wet chemical kitchen extinguishers generally follow a 5-year hydrostatic testing schedule. All types require annual professional maintenance under NFPA 10. A well-maintained commercial unit can outlast a neglected one by decades.

Where is the date on a fire extinguisher?

Look in three places: the neck or collar of the cylinder, where the manufacture date is often stamped or embossed into the metal; the label, where some manufacturers print the date; and the service tag, which shows a punched hole for the month and year of each professional inspection. No legible manufacture date means no documented history. Take the unit to a licensed technician for evaluation before returning it to service.

Is a 20-year-old fire extinguisher still good?

It depends entirely on its maintenance history. NFPA 10 sets no absolute age limit, but a 20-year-old unit must have passed both its six-year internal examination and at least one hydrostatic test on schedule to be considered serviceable. A commercial-grade Amerex or ANSUL extinguisher that has been professionally maintained with records to show it can pass inspection at 20 years and remain in service. One that has never been serviced should be retired and replaced.

Can an expired fire extinguisher be recharged?

In some cases, yes. If the cylinder passes hydrostatic testing, an NFPA 10-compliant technician can recharge and return it to service. The unit must first undergo internal examination if the six-year interval has passed. If the cylinder shows corrosion, structural defects, or fails pressure testing, recharging is not permitted and replacement is required.

Who is allowed to service a fire extinguisher in Texas?

Under Texas Administrative Code Title 28 Chapter 34 Section 34.5, only technicians licensed by the Texas State Fire Marshal’s Office may perform annual maintenance, six-year internal examinations, and hydrostatic testing on portable fire extinguishers. Industrial Fire holds the required Texas licenses (ECR-2061363 and ACR-2368800) and has been performing licensed extinguisher service in Houston since 1945.

Get your extinguishers inspected in Houston

Technician performing a professional fire extinguisher inspection at a Houston commercial property.

Industrial Fire has provided licensed fire extinguisher inspection, maintenance, recharge, and replacement services in Houston since 1945. The company holds Texas licenses ECR-2061363, ACR-2368800, B10568601, HCR-2215410, and RIN-A436, and is an authorized service provider for ANSUL, Amerex, Pyro-Chem, and Kidde extinguisher lines.

Walk-in customers can bring extinguishers directly to the Industrial Fire counter at 204 N Palmer St, Houston TX 77003, Monday through Friday, 8:00 a.m. to 3:30 p.m. For facilities requiring on-site service, 24/7 emergency service is available. Call (713) 223-9181 to speak with a licensed technician, or use the link below to schedule a fire extinguisher inspection.

Contact Industrial Fire to schedule your inspection or bring your extinguisher to our Houston counter.

Share this Article

About the Author

We are a family-owned and operated business. Industrial Fire has proudly served Houston, Texas, for over seven decades. Fire protection technology has changed a lot since we started doing business in 1945. Still, one thing hasn’t changed, our commitment to providing our neighbors in Houston, TX, with the best fire protection services and equipment available.